eGauge Meters
Connect the circuits on an eGauge meter, group them by category, and see them in your site's Equipment Energy Monitor, with history backfilled automatically.
Huckleberry can read interval data straight from an eGauge meter. Connect the registers you care about (each measured circuit or feed) and Huckleberry imports their history, then keeps polling for new readings. Electricity comes in as kWh per interval plus average kW. Water comes in by volume and is shown in gallons.
A guided setup walks you through the connection and shows you a sample of real readings before anything is saved. You can set up one register at a time, or tick several and set up a whole panel's circuits together.
Each register becomes its own meter. When you set up several registers at once, each still gets its own meter and its own connector, so you can rename, pause, or retire any one of them later without touching the others.
Before You Start
You'll need:
- The meter's HTTPS address. This is usually the eGauge proxy address,
https://<device-name>.egauge.io, or the meter's own public HTTPS address. Addresses that only work inside your building's network can't be reached by Huckleberry. - A username and password for the meter. A read-only account is enough.
- The site the meter serves, already set up in Huckleberry. If the site has a utility meter in Huckleberry, your circuits can be set up as its sub-meters (see Sub-meters).
Setting Up a Connector
Go to Admin → Data Connectors, choose + New connector, select eGauge meter, and click Next.

1. Site
Pick the site the meter serves. Its readings are stored on meters at this site.

2. Connect
Enter the meter's address, username, and password, then choose Test connection and discover registers. Testing saves nothing. The credentials are stored, encrypted, only when you activate the connector, and they're never shown again.

If the test fails, the message tells you why. Common causes:
- Wrong username or password. Check the credentials on the meter.
- Address not reachable. Use the
https://proxy address rather than a local network address.
3. Register
Huckleberry lists every register on the meter. Tick the ones to import. Tick one register to set it up on its own, or several to set up a panel's circuits together (see Setting Up Several Circuits at Once).

- Huckleberry decides what a register measures from its type on the meter, not from its name, so a register labelled "Water" that actually measures power is still treated as electricity.
- A register that's already imported by another connector is marked Already connected, with a link to that connector.
- A register that looks like the panel's own total (the meter's "use" register, or one named Main, Mains, Grid, Service, Total, or Usage) is marked as such. Leave it out when you're setting up the panel's circuits. If you do set it up, it's labelled Panel total, shown for reference, and never added to the circuits' totals, so nothing is counted twice.
The steps below describe setting up one register. With several ticked, Next takes you to a single batch step instead.
4. Units
This step shows what the register measures and how its readings are stored.

- Electricity registers are stored as kWh per interval, plus average kW. There's nothing to confirm.
- Volume registers can measure water, gas, or other flows. Confirm that the register measures water to continue. Water is stored by volume and shown in gallons. Gas and other volume registers aren't supported yet.
5. Solar & Flow
Huckleberry suggests values based on the register. Check them, because they decide how the meter counts in your totals.

| The register is… | Solar | Flow |
|---|---|---|
| The grid feed at a site with solar panels | Yes | Net |
| A solar (PV) inverter | Yes | Generation |
| A generator | No | Generation |
| A load or a whole-building feed | No | Consumption |
A Net register measures what's drawn from the grid minus what's exported, so some intervals can be negative. That's expected.
The solar question appears only for electricity.
6. Meter
Create a new meter at the site, or attach the register to an existing meter. Only meters that match the utility, flow, and solar choice, and that don't already receive readings from somewhere else, are offered.

- Sub-meter of. Choose the meter this circuit sits behind, usually the site's utility meter. Huckleberry pre-selects it when it can tell which one it is. A sub-meter's usage is already inside its parent, so site totals leave it out. Choose Not a sub-meter only if the circuit isn't behind any meter you have in Huckleberry. See Sub-meters.
- Category. The group this circuit belongs to in the site's Equipment Energy Monitor, such as Chillers, Lighting, or Headhouse Climate. Huckleberry suggests one from the register's name; type your own or pick one you've used before. Leave it blank and the circuit shows under Other.
- Give the meter and the connector a name.
7. Preview and Activate
Choose the reading interval (1 minute, 5 minutes, 15 minutes, or 1 hour) and how many days of history to backfill (up to 730).
Huckleberry runs a set of checks and reads a sample of real intervals from the meter. Nothing is saved yet. The sample shows the total, the time zone the meter reports in, how each value was calculated, and any gaps.

Registers that count backwards are fixed for you. Some eGauge installs record a circuit's usage as a negative number. Huckleberry spots this from the sample and flips the sign, so the circuit's readings come in as positive usage. The preview shows Sign when it has done this, and so does the connector's settings page afterwards.
When every check passes, choose Activate. Huckleberry starts importing the history right away, and then polls for new readings on the interval you picked.
Setting Up Several Circuits at Once
Tick two or more registers on the Register step and choose Next. One batch step replaces the rest of the guided setup.

- Sub-meter of applies to every electricity circuit that measures consumption. Huckleberry pre-selects the site's utility meter when it can. Generation, net, and water registers always stay standalone.
- Check each row. Each register has its own solar and flow choice, a meter name, and a category, all pre-filled from the register. Water registers need you to confirm they measure water.
- Preview all checks every row and reads a sample, one register at a time. Each row shows a tick and its last 24 hours of usage, or what went wrong.
- Activate all activates the rows one at a time. If one fails, the others still go ahead; fix the problem and choose Retry on that row, or Remove from batch to leave it out.
When every row is activated, choose Done. Each circuit now has its own connector under Data Connectors.
Sub-meters
A circuit measured by an eGauge is usually already counted by the site's utility meter. If both were added up, the same energy would be counted twice. Marking the circuit as a sub-meter of the utility meter prevents that:
- Site totals, including All Meters (total) on the Facility Management page, count only the main meter.
- The circuit is still shown on its own, listed under its parent in the meter dropdown, so you can look at it individually.
You can set or change a circuit's parent at any time on its connector's settings page.
Equipment Energy Monitor
Sites with eGauge circuits get an Equipment Energy Monitor on their Facility Management page. It shows where the site's energy goes, grouped by the categories you gave your circuits.

- Periods: Today, Yesterday, Last 7 Days, Last 30 Days, or a custom range of up to 400 days.
- kWh or kW: energy per interval, or average demand.
- Category chips: click a category to hide or show it in the chart and the table.
- The chart draws one line per category. A Panel total is drawn as a dashed reference line, so you can see how much of the panel your circuits account for.
- Summary by Category lists each category's usage for today, yesterday, the last 7 days, and the last 30 days. Click a row to see its circuits. A circuit that has stopped reporting shows N/A and is marked offline.
- Download CSV exports the table, one line per circuit plus a subtotal per category.
Times are shown in the site's own time zone. The monitor covers the whole site, even when you're looking at one building.
Watching the Import
Open the connector from Data Connectors to see how the import is going.

- Health and progress shows the connector's status, the last sync, and any failures in a row.
- Backfill and data shows how far back history goes, how much has been imported, and the latest reading stored. The bar fills as the backfill runs. A long history is imported over several runs.
- Gaps are periods where the meter had no data. Dropped resets and spikes are intervals Huckleberry left out because the meter's counter reset or jumped implausibly. Leaving them out keeps your totals accurate.
- Source shows the meter's details, including its clock. A large clock skew can make readings land in the wrong interval.
Use Sync now to run an import immediately, and Pause to stop polling for a while.
Changing a Connector
Some settings can be changed at any time: the connector's name, the flow, the solar choice, the sub-meter parent, the category, and how many days of history to backfill.

- A longer backfill reads further back. New readings keep arriving while the older history fills in over the next few runs, so your current data never pauses.
- A shorter backfill stops reading older history. If older history was still being filled in, Huckleberry stops at the new start.
- Category and sub-meter changes apply straight away to the Equipment Energy Monitor and to site totals.
The site, meter, register, utility, and interval are fixed, because changing them would mix readings from different sources. To change any of them, retire the connector and run the guided setup again.
Updating credentials. If the meter's password changes, enter the new username and password under Credentials. They're checked against the same meter before they replace the old ones.

Retiring a connector stops its imports permanently and frees the register. The meter and all of its readings are kept. Retiring can't be undone. To import the same register again, run the guided setup, which reuses the same meter.
How eGauge Readings Show Up
- Electricity meters appear with your site's other meters and count toward energy totals, charts, and exports according to the flow you chose. A sub-meter is shown on its own but left out of site totals, because its parent already counts it.
- Circuits with a category are grouped in the site's Equipment Energy Monitor. A Panel total is shown there for reference and never added up.
- Solar meters are counted as solar generation and are kept separate from the energy your buildings use.
- Water meters are shown in gallons and are never included in electricity totals, kWh charts, or energy exports.